Date Description Inspector Results Comments
05/08/2025 COT - RSBU - Preslab   Re-inspection required 1-Footing is less then 24” below adjacent grade as shown on detail A. 2-Footing only has 1#4 rebar instead of 2 as shown on detail A. 3-Footing is 12” wide instead of 16” shown on detail A.
05/13/2025 COT - RSBU - Preslab   Re-inspection required 1-Footing is still less than 16" wide. 2-Horizontal plumbing in footings must be sleeved.
05/14/2025 COT - RSBU - Preslab   Passed Passed 5/14/25 ok to pour concrete