Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Grounding/Bonding
| Date |
Description |
Inspector |
Results |
Comments |
| 05/08/2025 |
COT - RSEL - Grounding/Bonding |
|
Re-inspection required |
1-Footing is less then 24” below adjacent grade as shown on detail A. 2-Footing only has 1#4 rebar instead of 2 as shown on detail A. 3-Footing is 12” wide instead of 16” shown on detail A. |
| 05/13/2025 |
COT - RSEL - Grounding/Bonding |
|
Partial Pass |
underslab |
| 05/14/2025 |
COT - RSEL - Grounding/Bonding |
|
Partial Pass |
Partial pass for ufer only, will check connection at later date |
| 07/02/2025 |
COT - RSEL - Grounding/Bonding |
|
Passed |
Passed 7/2/25 |