Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Excavation/Rebar/Zoning
| Date |
Description |
Inspector |
Results |
Comments |
| 05/08/2025 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Re-inspection required |
1-Footing is less then 24” below adjacent grade as shown on detail A. 2-Footing only has 1#4 rebar instead of 2 as shown on detail A. 3-Footing is 12” wide instead of 16” shown on detail A. |
| 05/13/2025 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Re-inspection required |
1-Footing is still less than 16" wide. 2-Horizontal plumbing in footings must be sleeved. |
| 05/14/2025 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Passed |
Passed 5/14/25 ok to pour concrete |