Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-MDP-0824-00901

Parcel: 131093030


Addresses:

5627 E 29TH ST

Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Grounding/Bonding 

Date Description Inspector Results Comments
05/08/2025 COT - RSEL - Grounding/Bonding  Re-inspection required 1-Footing is less then 24” below adjacent grade as shown on detail A. 2-Footing only has 1#4 rebar instead of 2 as shown on detail A. 3-Footing is 12” wide instead of 16” shown on detail A.
05/13/2025 COT - RSEL - Grounding/Bonding  Partial Pass underslab
05/14/2025 COT - RSEL - Grounding/Bonding  Partial Pass Partial pass for ufer only, will check connection at later date
07/09/2025 COT - RSEL - Grounding/Bonding  Passed Passed 7/9/25