Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2025 | RSBU - Building Final | Re-inspection required | 3 March 25 1. Exterior GFCI outlets are on garage circuit. 2. GFCI outlet by condenser needs to be on its own circuit. 3. Birds screen on south side exhaust is not secured, it is lifting up. 4. Condenser pad needs to be 3'' above earth. |
|
| 03/06/2025 | RSBU - Building Final | Passed | 6 March 25 Pass |