Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
| Date |
Description |
Inspector |
Results |
Comments |
| 10/04/2024 |
COT - RSBU - Preslab |
|
Re-inspection required |
10/4/24: compaction at slab not complete, footing depth not per plan calls for 12" min, Masa clips not properly set/spaced, reinforcement overlaps not per plan, reinforcement AT ENTRY t&B must have a clearance of 2" from each other. |
| 10/09/2024 |
COT - RSBU - Preslab |
|
Passed |
10/9/24: Compaction is complete, masa clips are spaced evenly at 32" apart, rebar overlaps have been corrected. Okay to pour concrete. |