Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
Permit Number - TC-MDP-0824-00871
Inspection Description - COT - RSPL - Plumbing Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2025 | COT - RSPL - Plumbing Final | Re-inspection required | 7/8/25: vacuum breaker at hose bib required, exterior plastic piping must be coated for UV Protection, Mini split max fuses 15 Amp (30 amp installed), water heater max amp 54 (currently on 60 amp breaker), loft railing required, bathroom lav not complete, light fixtures must be properly installed, hose bib must be insulated and wrapped, INCLUSIVE HOME DESIGN NOTEs 1. PROVIDE AT LEAST ONE EXTERIOR ACCESSIBLE ROUTE AND ENTRANCE. ROUTE MAY ORIGINATE FROM CARPORT, DRIVEWAY, PUBLIC STREET, OR SIDEWALK. SLOPE OF THIS ROUTE SHALL NOT EXCEED ONE FOOT RISE PER TWENTY FEET HORIZONTAL DISTANCE (1:20), UNLESS A RAMP PER IRC IS CONSTRUCTED. NOTE: INDICATE THE "EXTERIOR ACCESSIBLE ROUTE" AND "ACCESSIBLE ENTRANCE" (ACC ENT) ON SITE PLAN. 2. ACCESSIBLE ENTRANCE: PROVIDE MINIMUM ONE NO-STEP LEVEL ENTRANCE THAT IS A MINIMUM 32 INCHES WIDE AND MEETS THE DOOR HARDWARE REQUIREMENTS PER THIS ORDINANCE. (NOT: EXIT DOORS ARE REQUIRED TO BE 36 INCHES MINIMUM AND THE GARAGE SHALL NOT BE USED AS AN EXIT). |
|
| 08/06/2025 | COT - RSPL - Plumbing Final | Passed | 8.6.25 Acceptable corrections made as requested Approved |