Inspection Status: Passed

Inspection History: COT - RSBU - Preslab  

Permit Number - TC-MDP-0824-00868

Inspection Description - COT - RSBU - Preslab  

Inspection Status - Passed

Date Description Inspector Results Comments
09/30/2024 COT - RSBU - Preslab   Passed Concrete forms are set, post tension cabling is evenly spaced, additional rebar reinforcement is in place per plan, Ufer ground is in place on side of garage, masa clips are evenly spaced at 32" on center, shear wall hold downs are placed per plan, all underground plumbing pipes are properly wrapped, and underground electrical outlets and conduit for kitchen island is installed. Okay to pour concrete.