Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0823-01453

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/23/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9/23/24: Anchor bolts need to be placed 12" from edge where MASA clips are installed with 2 legs up, 1 in 3 MASA clips can have 1 leg up (multiple locations where 1 in 3 is exceeded), interior non bearing walls must be properly fastened at sill plate no greater than 36" o.c, bracing at trusses missing per clacs, front entry way column needs to be properly supported, no roof access.
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass 9/26/24: missing some anchor bolts at exterior will check for them at intermediate
11/05/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 11-5-24, anchor bolts in question from previous inspections verified as per approved plans.