Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: RSBU - Building Progress

Permit Number - TC-MDP-0823-01450

Inspection Description - RSBU - Building Progress

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/31/2024 RSBU - Building Progress Re-inspection required 7/31/24: irrigation breaker not installed, "for future solar" required at panel,secure electrical whip at irrigation, fencing not installed at time of inspection, 6" min from weep screed to grade , UV tape hose bib, gray water clean outs must be cut to grade and capped, Pad at A/C condenser needs 3" clearance form grade on all sides, high loop at dishwasher must be installed, no attic access, Tempered glass not installed at master shower, garage door rating tag has been painted over,
08/07/2024 RSBU - Building Progress Passed