Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Permit Number - TC-MDP-0823-01450

Inspection Description - COT - RSME - Mechanical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/31/2024 COT - RSME - Mechanical Final  Re-inspection required 7/31/24: irrigation breaker not installed, "for future solar" required at panel,secure electrical whip at irrigation, fencing not installed at time of inspection, 6" min from weep screed to grade , UV tape hose bib, gray water clean outs must be cut to grade and capped, Pad at A/C condenser needs 3" clearance form grade on all sides, high loop at dishwasher must be installed, no attic access, Tempered glass not installed at master shower, garage door rating tag has been painted over,
08/07/2024 COT - RSME - Mechanical Final  Passed 8/7/24: All items from last inspection have been corrected or cleaned. Mechanical, electrical, and plumbing fixtures are installed and properly working. Electrical panel is properly labeled with correct breaker sizes installed. Okay to issue Certificate of Occupancy once Fire and engineering complete their inspections.