Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - TC-MDP-0823-01422

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/13/2024 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required 9/13/24: ALL LISTED ITEMS WERE FOUND ON FIRST FLOOR EAST UNIT. STOPPED INSPECTION. Anchor bolt spacing at Shearwalls not per plan, anchor bolts must be properly fastened, holdowns must be properly fastened, Anchor bolts required 12" from edge of sill plate, Web stiffeners must be properly fastened, missing web stiffeners throughout,post to beam connections not per plan, SW1 schedule fasteners not per schedule, Missing jack/king studs at openings. field modified TJI must be repaired/replaced. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
09/25/2024 COT - RSBU - Exterior Clips/Sheathing  Passed