Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - TC-MDP-0823-01401
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2024 | COT - RSBU - Exterior Clips/Sheathing | Passed | ||
11/06/2023 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | 11/6/23: anchor bolts are required within 12" of end of shear walls. Hold-downs are NOT anchor bolts and can not serve as both engineering requirements. |