Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
Permit Number - TC-MDP-0823-01372
Inspection Description - BULD - Electrical Clearance
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2023 | BULD - Electrical Clearance | Re-inspection required | GEC installed to Uffer incorrectly, use proper clips to hold down low voltage plastic conduit, use proper nail plates at top plate for orange conduit, open chase right side of garage opening, garage lights must be on it’s own circuit. Cannot connect to inside of house, wiring must be protected by continuous sheathing. Wiring behind dryer hood vent at laundry, laundry receptacles must be of 12 gauge 20amp GFCI, nail plate needed in room behind garage shear wall and foam electrical box, foam penetration at blocking at stairs, foam top plate in bedroom, properly secure wiring in mechanical room and properly secure base for platform, foam top plate throughout. | |
12/06/2023 | BULD - Electrical Clearance | Passed | TEP ECO Clearance issued. Okay to energize system. |