Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 141450700

Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Permit Number - TC-MDP-0823-01372

Inspection Description - BULD - Electrical Clearance

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/29/2023 BULD - Electrical Clearance Re-inspection required GEC installed to Uffer incorrectly, use proper clips to hold down low voltage plastic conduit, use proper nail plates at top plate for orange conduit, open chase right side of garage opening, garage lights must be on it’s own circuit. Cannot connect to inside of house, wiring must be protected by continuous sheathing. Wiring behind dryer hood vent at laundry, laundry receptacles must be of 12 gauge 20amp GFCI, nail plate needed in room behind garage shear wall and foam electrical box, foam penetration at blocking at stairs, foam top plate in bedroom, properly secure wiring in mechanical room and properly secure base for platform, foam top plate throughout.
12/06/2023 BULD - Electrical Clearance Passed TEP ECO Clearance issued. Okay to energize system.