Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
| Date |
Description |
Inspector |
Results |
Comments |
| 08/29/2024 |
COT - RSPL - Plumbing Final |
|
Re-inspection required |
Breaker over amped provide 40. Provide lock out at water heater breaker. Secure seal tight whip. Leak at dishwasher. Replace broken roof tiles. 8/29/2024 |
| 08/30/2024 |
COT - RSPL - Plumbing Final |
|
Passed |
8/30/24: 40 amp breaker installed for A/C unit, lock-out bar installed on hot water breaker, and seal tight whip on A/C has a second strap attached. Leak at dishwasher has been corrected. Broken roof tiles have been replaced. Okay to issue Certificate of Occupancy. |