Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - TC-MDP-0823-01357
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Canceled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2023 | COT - RSBU - Exterior Clips/Sheathing | Canceled | 10/30/23: canceled by contractor | |
11/02/2023 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | Headers not per plan, fix headers for entrance of garage, front and back porch headers, apply headers per plan., missing anchor bolts at shear walls. Anchor bolts at Shear walls SW11 and greater must be installed with 3x3” plate washers or greater per plans, add shot pins to some plates at master bathroom, add shot pins throughout, foundation for back porch pillar cracked, anchor bolts missing throughout, add straps to connect trimmer and header throughout. | |
11/08/2023 | COT - RSBU - Exterior Clips/Sheathing | Passed | 11/8/23: Contractor Superintendent Karl Chlarson has a letter from the engineer approving the larger size headers at garage entrance and front/rear porch entrance. Anchor bolts with 3x3 plate washers have been installed in shear wall SW11, shot pins have been installed at all locations marked with an X on sole plate. Straps have been installed to the headers and trimmer locations. Okay to proceed with roof and exterior wall dry-in. |