Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
front garage not ready, anchor bolts missing at front garage, sister stud at left side of garage, missing anchor bolts at shear walls and perimeter of house, shear walls sw11 and greater must have anchor bolts installed with 3”x3” plate washers per plans, add nails to interior sole plates where marked in red throughout, replace 2x6 sole plate between kitchen and master bathroom marked in red. |
| 11/01/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|