Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Date Description Inspector Results Comments
09/24/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 9/24/26: seal vapor barriers throughout- a few areas were marked, fire foam penetration at top plate near back sliding glass door, add nail plates at marked location & where closer than 1 1/4" from stud edge, secure pre line behind tub, add FHA plate at kitchen exhaust, provide supports above ceiling for restroom exhausts & DWV, add supports to ducts at 4' Intervals, tape duct tear at garage.
09/25/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 9-25-26 secure cold waterline behind tub* at marked locations add supports to ducts at 4' Intervals* DWV not under the test
09/29/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 9-29-26 all corrections have been made OK to proceed