Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Excavation/Rebar/Zoning
| Date |
Description |
Inspector |
Results |
Comments |
| 08/18/2026 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Re-inspection required |
8-18-26 tendons at stationary ends through should have a minimum of 12" exposure please use approved methods to correct. Footer at east end should be a minimum of 12" no loose dirt or other debris. Re inspection is required. |
| 08/19/2026 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Re-inspection required |
8-19-26 tendons at stationary ends throughout should have a minimum of 12" exposure please use approved methods to correct. Footer at east end should be a minimum of 12" no loose dirt or other debris. Re inspection is required. |
| 08/20/2026 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Canceled |
8-20-26 Due to wet conditions, unable to verify footer depth |
| 08/21/2026 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Passed |
8-21-26 all corrections have been made OK to pour |