Permit: TC-MDP-0726-00605

Parcel: 141156730


Addresses:

9948 E LEBARON DR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Preslab  

Date Description Inspector Results Comments
08/18/2026 COT - RSBU - Preslab   Re-inspection required 8-18-26 tendons at stationary ends through should have a minimum of 12" exposure please use approved methods to correct. Footer at east end should be a minimum of 12" no loose dirt or other debris. Re inspection is required.
08/19/2026 COT - RSBU - Preslab   Re-inspection required 8-19-26 tendons at stationary ends throughout should have a minimum of 12" exposure please use approved methods to correct. Footer at east end should be a minimum of 12" no loose dirt or other debris. Re inspection is required.
08/20/2026 COT - RSBU - Preslab   Canceled 8-20-26 Due to wet conditions, unable to verify footer depth
08/21/2026 COT - RSBU - Preslab   Passed 8-21-26 all corrections have been made OK to pour