Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-0725-00387
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 10.21.2025 Missing toenails on floor truss to top plate throughout, missing 2x ledger at front of garage, add anchor bolts at marked locations, add toenails to roof truss screws per detail SD2-1 throughout, add screws triple girder truss second floor as marked, add truss screws at marked locations or H1 clip to split truss. |
|
| 10/24/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 10.24.2025 Corrections made to 10.21.2025 inspection. |