Permit: TC-MDP-0724-00848

Parcel: 137322850


Addresses:

5583 S SWIRES RD

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
01/26/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 1-26-26: add shot pins 24" o.c., missing backing/reinforcement at restrooms,
Add nails to marked locations at exterior sheathing-north side, add anchor bolts to marked locations, add nails to loose roof panels at marked locations. Make corrections and reschedule an inspection.
Note: front & rear framing not done-porches not yet installed.
01/27/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass 1-27-26: Partial pass pending framing on porches. Also, restroom backing not yet installed but will verify at upcoming framing inspection. Okay to continue with construction at progress areas.
02/02/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 2-2-26: missing LUS26 hangers, 2 anchor bolts are required at column sill plate ( plate 12" or more in length require 2 a/b's), submit an updated floor plan showing removal of third column at back patio, provide clarification on whether lag screws are required at ledgers for front/rear patios, add CS20 strap at columns (post to beam).
02/04/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 2.4.26
Cs20 still required per previous notes
Lus28 hangars to be installed per manufacturer specs