Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - TC-MDP-0724-00794
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2024 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | Provide address tag. 11/20/2024 | |
11/21/2024 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | Provide address tag. 11/20/2024 11/21/24: Anchor bolt spacing not per schedule, anchor bolts spacing at shear walls not per schedule, hold down missing at shear wall at patio next to SGD, shearwalls not fastened per schedule. Stairs not framed per plans. Workers in house, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
|
11/26/2024 | COT - RSBU - Exterior Clips/Sheathing | Passed | Ok to cover exterior walls |