Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-MDP-0724-00794
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2024 | COT - RSBU - Roof Nailing | Re-inspection required | Provide address tag. 11/20/2024 | |
11/21/2024 | COT - RSBU - Roof Nailing | Re-inspection required | Provide address tag. 11/20/2024 11/21/24: Anchor bolt spacing not per schedule, anchor bolts spacing at shear walls not per schedule, hold down missing at shear wall at patio next to SGD, shearwalls not fastened per schedule. Stairs not framed per plans. Workers in house, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
|
11/26/2024 | COT - RSBU - Roof Nailing | Passed | OK to dry-in roof system |