Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Interior Shear Bracing
Permit Number - TC-MDP-0724-00791
Inspection Description - COT - RSBU - Interior Shear Bracing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2024 | COT - RSBU - Interior Shear Bracing | Re-inspection required | 10/7/24: anchor bolts at shear-walls and exterior walls not per plan, properly fasten all anchor bolts, rsp4 not per plan, detail S2.1/14 missing on plans at interior bearing walls. Shot pins required 6" from edge of sill plate, shot pins required 36" o.c | |
11/14/2024 | COT - RSBU - Interior Shear Bracing | Partial Pass | 10/7/24: anchor bolts at shear-walls and exterior walls not per plan, properly fasten all anchor bolts, rsp4 not per plan, detail S2.1/14 missing on plans at interior bearing walls. Shot pins required 6" from edge of sill plate, shot pins required 36" o.c 11/14/24: partial pass for 5/8 type x on exterior above roof line on fire wall ok to proceed. |