Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - TC-MDP-0724-00790
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2024 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | Provide address tag. 11/20/2024 | |
11/21/2024 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | Provide address tag. 11/20/2024 11/21/24: Anchor bolt spacing not per plan, anchor bolts required at interior bearing walls, anchor bolts required 12" from edge of sill plate, anchor bolts must be located in middle third of width of plate. RSP4 required on north wall, H2.5 must be properly fastened, CS16 straps at garage must be 54" in length currently 48", LSTHD 8 required at back patio entrance. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |