Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
| Date |
Description |
Inspector |
Results |
Comments |
| 10/25/2024 |
COT - RSBU - Preslab |
|
Re-inspection required |
10/25/24: reinforcement at garage south wall missing per plans, reinforcement missing at slope at garage, UFER needs to be moved to address future electrical panel clearance , damaged sheathing needs to be repaired, thickened slab required at interior holdowns, exterior footings reinforcement not per plan |
| 10/28/2024 |
COT - RSBU - Preslab |
|
Passed |
Corrections made 10/28/24 |