Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-MDP-0724-00790
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2024 | COT - RSBU - Roof Nailing | Re-inspection required | Provide address tag. 11/20/2024 | |
11/21/2024 | COT - RSBU - Roof Nailing | Re-inspection required | Provide address tag. 11/20/2024 11/21/24: Anchor bolt spacing not per plan, anchor bolts required at interior bearing walls, anchor bolts required 12" from edge of sill plate, anchor bolts must be located in middle third of width of plate. RSP4 required on north wall, H2.5 must be properly fastened, CS16 straps at garage must be 54" in length currently 48", LSTHD 8 required at back patio entrance, nailing at shearwall not per schedule. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |