Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 132131860


Addresses:

2667 S AYALA ST


Inspection Status: Canceled

Inspection History: COT - RSPL - Plumbing Final 

Permit Number - TC-MDP-0724-00789

Inspection Description - COT - RSPL - Plumbing Final 

Inspection Status - Canceled

Date Description Inspector Results Comments
03/21/2025 COT - RSPL - Plumbing Final  Canceled
04/10/2025 COT - RSPL - Plumbing Final  Re-inspection required 4/10/25: Knock-outs at main panel must be sealed, liquid tight at irrigation system must be secured, 1/2" conduit at irrigation box must be secured, exposed in treated wood must be treated at final inspection, hose bibs must be insulated, hot water lines at garage must be insulated, post tension tag required at exterior hose bib, garage must be self closing and rated, secure gas line under range, high loop at dishwasher must be properly secured, properly secure electrical whip for oven and install faceplate, GFCI required at bathrooms, plumbing fixtures not installed. Exterior plastic piping must be coated for UV protection, all faceplates at boxes must be properly installed, WR receptacles required on exterior of home . STOPPED INSPECTION MORE ITEMS MAY BE ADDED (second floor was not inspected)
04/18/2025 COT - RSPL - Plumbing Final  Passed 4-18-26, plumbing & building final approved