Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSPL - Plumbing Final
Permit Number - TC-MDP-0724-00789
Inspection Description - COT - RSPL - Plumbing Final
Inspection Status - Canceled
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2025 | COT - RSPL - Plumbing Final | Canceled | ||
| 04/10/2025 | COT - RSPL - Plumbing Final | Re-inspection required | 4/10/25: Knock-outs at main panel must be sealed, liquid tight at irrigation system must be secured, 1/2" conduit at irrigation box must be secured, exposed in treated wood must be treated at final inspection, hose bibs must be insulated, hot water lines at garage must be insulated, post tension tag required at exterior hose bib, garage must be self closing and rated, secure gas line under range, high loop at dishwasher must be properly secured, properly secure electrical whip for oven and install faceplate, GFCI required at bathrooms, plumbing fixtures not installed. Exterior plastic piping must be coated for UV protection, all faceplates at boxes must be properly installed, WR receptacles required on exterior of home . STOPPED INSPECTION MORE ITEMS MAY BE ADDED (second floor was not inspected) | |
| 04/18/2025 | COT - RSPL - Plumbing Final | Passed | 4-18-26, plumbing & building final approved |