Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - TC-MDP-0723-01285
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/21/2024 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | Missing second king stud at each end at flex room window, hallway and master bedroom entrances with 4x6 headers missing 2-2x6 studs at each end per plans, missing third lateral bracing for trusses A4, Truss A6 and A7 missing lateral bracing, missing rsp4 clip at front porch. | |
03/25/2024 | COT - RSBU - Exterior Clips/Sheathing | Passed | 3/25/24: King studs have been added at window, hallway, and master bedroom entrances. Lateral bracing has been added for trusses A4, A6, & A7. RSP Clip has been installed at front porch. Okay to proceed with roof dry in and exterior stucco dry in. |