Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 1/10/24: SW1 not per plan throughout. Openings greater than 5’ requires 2king and 1jack studs per IRC table 603.694, header at master bathroom not per plan, studs notched greater then 25% at bottom plate need sister stud , beam post connection at back porch not per plan, anchor bolts is greater than max spacing is 32” O.C per plan throughout, plans call for 2x4 at 24” O.C at exterior walls installed are 2x6 at 24”O.C, exterior walls have spans greater than 24”O.C throughout, shot pins at interior walls greater than 12” from edge of bottom plate, shot pins at bottom plate over spanned at interior walls. STOPPED INSPECTION MORE ITEMS MAY BE ADDED | ||
| 01/12/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Partial Pass | 1/10/24: SW1 not per plan throughout. Openings greater than 5’ requires 2king and 1jack studs per IRC table 603.694, header at master bathroom not per plan, studs notched greater then 25% at bottom plate need sister stud , beam post connection at back porch not per plan, anchor bolts is greater than max spacing is 32” O.C per plan throughout, plans call for 2x4 at 24” O.C at exterior walls installed are 2x6 at 24”O.C, exterior walls have spans greater than 24”O.C throug 1/12/24:SW1 missing per plan, beam/post connection at back porch not per plan. All other connections were made. |
|
| 01/16/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed |