Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 01/17/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
1/17/24: anchor bolts spacing shall not exceed 32" O.C (over spanned throughout), shearwall schedule not per plan (lengths are not met per plan), plans call for 6"x6" wood post as supporting means at back porch GLB on both sides (missing on one end). |
| 01/18/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|