Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 11/03/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Missing second cs16x5 at garage, add nails to shear wall stud, shear walls missing anchor bolts, all shear wall anchor bolts must be installed with 3x3” plate washers, blocking needed at horizontal open chase at second floor front of house pop out. Top of window. |
| 11/07/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Not ready. |
| 11/09/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Missing second cs16x5 at garage, all shear wall anchor bolts must be installed with 3x3” plate washers, Anchor bolts loose. Tighten all anchor bolts throughout. |
| 11/13/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Partial Pass |
Missing anchor bolts at garage and family room shear wall, shear wall anchor bolts to be installed with minimum 3x3” plate washers per plans. Not 2x2'' plate washers. Partial Pass. Ok to proceed. Check at intermediate. |
| 11/17/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|