Permit: TC-MDP-0626-00441

Parcel: 141461890


Addresses:

9601 E WYNALDA DR

Inspection Status: Not Ready

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
07/29/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready Plans are incomplete. Provide updated Model approved plans. Blowout at holdown at garage entry. No less than 1” minimum. Requires engineer fix. Windows in place prior of approval for framing inspection. Nailing required at jack studs to be 8” o.c to king studs. Riser exceeding 3/8”. Nosing exceeding 1 1/4” at last step. Stopped inspection. Other items may apply. 7/29/2026
08/03/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass 08/03/2026
Corrections made. Partial pass pending fix to front of garage foundation damage.