Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
11/18/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 11.18.25
Improper nailing pattern at exterior sheathing throughout.
Nails over penetrate throughout sheathing
Nails shall be no closer to 3/8" from the edge of panel
Missing anchor bolts at corners
Missing shot pins at splices/ends (must be within 6 inches of ends)
Please note: clips and sheathing has not yet been passed, electrical and mechanical rough in was in progress when inspector arrived on site. Do not proceed with work until previous inspection is passed.
11/20/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 11/20/2025 corrections were made.