Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 141461780


Addresses:

7311 S DEMPSEY AV


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0625-00349

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/31/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Trimmers for sliding glass door need to be continuous. Rsp clips missing East end of dwelling. Add anchor bolts at marked areas. Hold down at garage not nailed. Provide engineer fix. Add h25 at girder truss near stairs. (Both ends) Shim bearing points in garage area. Add studs to girder truss from top to bottom for load transfer. Add blocking at belly band seams for nailing schedule. Both girder trusses are floating and not bearing on wall. Blocking at entry above header north end needs corrections. Stopped inspection. Walked first floor only. Other items may apply. 7/31/2025
08/04/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 8.4.25
Corrections made as requested in previous inspectors report. No additional items found.