Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Not Ready | ||
| 10/09/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Provide set of approved plans for inspection. 10/9/2024 | |
| 10/10/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Provide set of approved plans for inspection. 10/9/2024 10/10/24: properly fasten anchor bolts throughout, shot pins required 4' o.c and 6" from edge of sill plate at interior walls, anchor bolts required 12" from edge of sill plate, cut access panel at porch columns to ensure proper hold downs and supports, shims required at trimmer studs not making full contact with headers, sheathing fasteners must be 3/8" from edge and shall not penetrate more than 1/8". |
|
| 10/11/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | Corrections were made. 10/11/2024 |