Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 10/15/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
10/15/24: missing anchor bolt at bottom plate south east corner. Rsp clips missing on west side and east side of home. Bearing points for girders need to have studs installed to support both front and back of home. H25 clip missing on west side of home at trust in bathroom. more items can be added. |
| 10/21/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
10/21/24: Anchor bolts have been installed, RSP Clips are installed where missing, studs have been added at girders, and H2.5 clips have been installed where missing. Okay to proceed with rough-in of M, P, AND E. |