Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof NailingĀ 

Date Description Inspector Results Comments
10/04/2024 COT - RSBU - Roof NailingĀ  Re-inspection required 10/4/24: Anchor bolts missing at garage perimeter wall per detail 8/S4.1, RSP4 missing on east side of home exterior wall, Shear wall anchor bolt spacing not per plan. STOPPED INSPECTION MORE ITEMS MAY BE ADDED
10/11/2024 COT - RSBU - Roof NailingĀ  Passed 10/9/24: Anchor bolts have been installed in shear wall and garage perimeter wall. RSP Clips have been added where missing. Okay to proceed with rough-in.