Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0624-00738

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
10/25/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Missing rsp4's east wall, add anchor bolt where marked (east wall), shot pins missing throughout interior framing (one shot pin shall be installed at 6 inches from each end of each sill plate.)Missing t-15 on truss calculations-verify truss calcs.,add nails to straps on north end of building. Stopped inspection, additional items requiring correction may be noted.
10/31/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 10-31-24, listed items from previous inspection have been corrected. Roof nailing inspection approved. Okay to continue with construction.