Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
| 11/01/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
11-1-24, not ready. Missing breakers at panel, not grounded to ufer, no gas gauge , and workers still working in building. |
| 11/05/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
11-5-24, add bank plate at marked area in laundry room, missing fire foam where gas line penetrates top plate in laundry room, patio metal box not grounded, a 12 inch clearance is required from pex to lights above lavatory in master suite, add fire foam to upstairs chutes to include at soft ducts and behind bathtub. |
| 11/06/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Passed |
11-6-24, listed items from previous inspection have been corrected. Intermediate inspection approved. |