Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Permit Number - TC-MDP-0624-00715

Inspection Description - COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/19/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 11/19/Add blocking to air ducts in laundry room and at entrance to first floor bedroom. Add fire blocking at all penetrations between floors and mechanical chase second floor. Seal all vapor barrier penetrations. Replace stud at communication box. Header in the laundry room are comprised, replace dryer vent box. Exhaust pvc not full on second floor. Nail plates throughout, I marked where you need them. Straps needed at first floor bedroom bathroom. No greywater 2" outlet at laundry room.
11/21/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 11-21-24, listed items from previous inspection corrected. Okay to proceed with construction