Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Permit Number - TC-MDP-0624-00711

Inspection Description - COT - RSBU - Roof Nailing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/25/2024 COT - RSBU - Roof Nailing  Re-inspection required 9/25/25: Anchor bolts must have a minimum of 7 fasteners to be considered properly installed, RSP.4 missing at garage entry south wall, king studs at SLD not per plan, H2.5 required at truss, shear wall fasteners not per schedule, anchor bolt required 12" from edge of sill plate at shearwalls, truss bracing required throughout, shims required at interior bearing walls at top plate, roof nailing not per schedule.
09/27/2024 COT - RSBU - Roof Nailing  Passed passed