Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-MDP-0624-00711
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2024 | COT - RSBU - Roof Nailing | Re-inspection required | 9/25/25: Anchor bolts must have a minimum of 7 fasteners to be considered properly installed, RSP.4 missing at garage entry south wall, king studs at SLD not per plan, H2.5 required at truss, shear wall fasteners not per schedule, anchor bolt required 12" from edge of sill plate at shearwalls, truss bracing required throughout, shims required at interior bearing walls at top plate, roof nailing not per schedule. | |
| 09/27/2024 | COT - RSBU - Roof Nailing | Passed | passed |