Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof NailingĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 09/25/2024 |
COT - RSBU - Roof NailingĀ |
|
Re-inspection required |
9/25/25: Anchor bolts must have a minimum of 7 fasteners to be considered properly installed, RSP.4 missing at garage entry south wall, king studs at SLD not per plan, H2.5 required at truss, shear wall fasteners not per schedule, anchor bolt required 12" from edge of sill plate at shearwalls, truss bracing required throughout, shims required at interior bearing walls at top plate, roof nailing not per schedule. |
| 09/27/2024 |
COT - RSBU - Roof NailingĀ |
|
Passed |
passed |