Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-MDP-0623-01201
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2024 | COT - RSEL - Electrical Final | Re-inspection required | 4/1/24: Cut clean-outs to grade and cap, exterior plastic piping must be coated for uv protection, YWL must be properly insulated and wrapped, kitchen requires 2. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. | |
04/03/2024 | COT - RSEL - Electrical Final | Re-inspection required | Receptacles installed in kitchen must be supplied by two separate branch circuits per E3901.3.2. | |
04/05/2024 | COT - RSEL - Electrical Final | Passed |