Parcel: 10319001T


Addresses:

2360 W OWL PERCH LP


Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-MDP-0623-01201

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/01/2024 RSBU - Building Final  Re-inspection required 4/1/24: Cut clean-outs to grade and cap, exterior plastic piping must be coated for uv protection, YWL must be properly insulated and wrapped, kitchen requires 2 circuits. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
04/03/2024 RSBU - Building Final  Re-inspection required Receptacles installed in kitchen must be supplied by two separate branch circuits per E3901.3.2.
04/05/2024 RSBU - Building Final  Passed