Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
Permit Number - TC-MDP-0623-01185
Inspection Description - RSBU - Building Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/21/2024 | RSBU - Building Final | Re-inspection required | Garage and exterior outlet receptacles must run on their own circuits per E1 plans, countertop right side of range missing gfci receptacle per E3901.4, kitchen outlets missing plate covers. Not ready. Stopped inspection. More items may be added. | |
03/26/2024 | RSBU - Building Final | Passed |