Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Date Description Inspector Results Comments
03/11/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 1. Bang plates needed throughout.
2. Vent on West wall second floor bathroom needs Boca plate on sill and on top plate, also needs to be sealed/flashed through roof.
3. Pancake box in master bathroom above sink is overloaded.
4. Attic light switch needs to be facing attic access, current location is hard to find in the dark.
5. Return air flex for bedroom 3 is not attached to Air handler.
03/13/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 13 March 25
Pass