Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 08/01/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
8-1-25: add anchor to marked location, missing cross bracing at middle point of home-plans call for it every 25' o.c., missing truss calcs, add shot pins every 24" o.c. And within 6" at end of each plate-minimum of 2 shot pins per plate, add nails to exterior sheathing at marked locations where over penetrated -nails cannot be closer than 3/8" from edges/joints. |
| 08/04/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
8-4-25: exterior clips/sheathing approved. |