Parcel: 141433360

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Permit Number - TC-MDP-0623-01159

Inspection Description - COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
06/03/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 6/3/24: ground screw missing throughout at metallic fixtures, truss bearing/shear transfer detail missing at entrance per plan (SD-2/1B), all penetrations going through top plate need to be sealed, all penetrations going through vapor barrier must be sealed, nail plate missing throughout at plumbing and electrical, seal all penetrations through second floor decking, PV conduit must be stubbed through roof, properly secure flex duct, properly support PV conduit midway, properly seal chase upstairs, properly secure electrical at boxes, cleanout missing at second floor bathroom in master,
06/05/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed