Inspection Status: Not Ready

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
01/03/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready
01/04/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Canceled 1/4/24: canceled per contractor
01/09/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required (with fee) Add nails to h2.5 clip at left side of garage, missing anchor bolts back left shear wall and Sthd hold down not nailed to shear wall. Engineer fix required, missing rsp4 clips top plate of second floor window right side of house. House has proceeded to intermediate and been lathed before passing intermediate. Re-inspection with fee required.
01/11/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Canceled Cancelled per Trent.
01/12/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass Missing rsp4 clips top plate of second floor window right side of house. Check at intermediate.
01/19/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed
11/21/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Sthd hold down left side of garage over spalled, add nails to h2.5 clip at left side of garage, Sthd hold down at front porch door misplaced. Add appropriate HTT hold down substitute, missing anchor bolts back left shear wall and Sthd hold down not nailed to shear wall. Add HTT substitute, missing rsp4 clips top plate of second floor window right side of house.